Skip to main content
0800 0016328
Fire Door Range

HMO Licensing · RRO 2005 · LACORS Guide

HMOs

Fire doors for hmos

Houses in Multiple Occupation (HMOs) are some of the most heavily regulated residential properties in the UK. Mandatory licensing applies to most HMOs of 5+ occupants, and many councils operate additional and selective licensing schemes covering smaller HMOs and single-let properties. Every licensed HMO must have fire doors fitted at the entrance to each habitable room — bedrooms, kitchens, and living rooms — and on all routes onto the protected escape stair.

FD30S fire door at every bedroom and habitable room entrance
Smoke seals required — councils consistently fail HMOs without them
Intumescent strips around all three rebated edges (head + both jambs)
Self-closing device on every fire door — must close from any angle
Doors must close into the latch fully without manual assistance
Required under the Management of HMOs (England) Regulations 2006

Recommended specification: FD30

Standard 4-6-bed HMOs need FD30S throughout. Larger or multi-storey HMOs (typically 7+ occupants, 3+ storeys) may need FD60S on doors onto the protected stair — confirm with the licensing officer at inspection. Make sure every door has the correct closer and smoke seals; these are the two most common failure points at licensing inspection.

Fire doors suitable for hmos

Certified to BS 476 Part 22 · full documentation supplied · 2-3 week lead time

FAQ

Fire doors for hmos — common questions

What fire doors do I need for a 5-bed HMO?

A standard 5-bed HMO under mandatory licensing requires FD30S fire doors at every bedroom and habitable room entrance, including the kitchen, with smoke seals around all three rebated edges. The doors must be fitted with a certified self-closer that closes the door from any angle of opening. Frame and ironmongery must match the door's test evidence.

Do single-let properties need fire doors?

Single-family dwellings under standard tenancies do not legally require fire doors at internal doors, but they do at flat entrance doors in shared corridors. If the property is in a council area operating additional or selective licensing covering single-let properties, fire safety standards including fire doors may apply — check your council's licensing conditions.

Will my HMO licence be refused if a fire door has no smoke seals?

In most council schemes, yes — smoke seals are explicitly required under both the LACORS Housing Fire Safety Guidance and most HMO licensing schemes. Doors fitted with intumescent strip only (no brush or fin smoke seal) routinely fail inspection. Replace with FD30S doors that have integrated smoke seals from the factory rather than retrofitting separate strips.

How quickly can I get HMO-compliant fire doors delivered?

Standard FD30S fire doors are typically delivered to mainland UK addresses within 2-3 weeks of order confirmation. We supply all standard sizes off the shelf; made-to-measure doors for non-standard openings have the same 2-3 week lead time. Full HMO licensing documentation (BS 476-22 certificate, intumescent and smoke seal data sheets) is supplied alongside the delivery.

Get a quote

Fire doors for hmos — get a free quote

Tell us how many doors you need, the rating, and the delivery address. We'll come back with pricing, lead time, and a documented specification suitable for your building safety case.

Standard lead time 2-3 weeks · £140 flat-rate UK delivery